How to arrange the generator room

2025-08-01 Visits:1
Regulations for Rational Layout of Generator Set Rooms:
Generator set rooms can be arranged on the first floor or the basement floor, and the following measures shall be taken:

 

  1. Diesel generator rooms shall be separated from other areas by partition walls with a fire resistance rating of not less than 2.00 hours and floor slabs with a fire resistance rating of not less than 1.50 hours.
  2. An independent oil storage room shall be set up, with an oil storage capacity not exceeding the 8-hour demand. Measures shall be taken to prevent leakage and oil spillage, and the oil tank shall be equipped with a vent pipe (connected to the outdoors). The oil storage room shall be separated from the generator room by a fire wall; if a door must be installed in the fire wall, a self-closing Class A fire door shall be provided.
  3. Independent fire separation shall be adopted, and fire compartments shall be divided separately.

 

Configuration of Fire-Fighting Facilities:

 

  1. Fire hydrants, fire hoses, and fire nozzles are installed outside the room.
  2. Oil-type fire extinguishers, dry powder fire extinguishers, and gas fire extinguishers are placed inside the room.
  3. Prominent "No Open Flames" safety signs and text are displayed.
  4. A dry fire sand pool is provided inside the room.
  5. Isolation measures shall be taken from oil depots.
  6. The distance between the generator set and buildings or other equipment shall be at least 1 meter, and good ventilation shall be maintained.
  7. Emergency lighting and emergency indicators shall be installed; for basement rooms, independent ventilation and fire alarm devices shall also be equipped.

 

Case Analysis:
An example of installation for a customer involves a 1200kW diesel generator set, with engineers assisting in installation and commissioning. Vibration-damping rubber pads are placed between the generator set base and the ground. Ventilation holes are opened on the wall directly opposite the water tank, and exhaust pipes are connected to the outdoors. The distance between the unit and the wall is over 2 meters, ensuring heat dissipation and facilitating maintenance. An MNS-type low-voltage switchgear is also equipped, which can perform real-time monitoring and control of parameters such as current, voltage, and power, ensuring the stable and safe operation of the power system. This room can be regarded as a model for generator set rooms.